Electrical and Fuel Inlet Locations
The 3/4 inch N.P.T. fuel inlet connector
A
and electrical inlet
location
B
is shown below.
A ½ inch knock-out is provided for the electrical inlet. This
inlet may be enlarged or supplemented to accommodate
a maximum conduit size of 1 ½ inches. Ensure that the
installed conduit(s) enter the unit in the zone shown in the
drawing such that they properly enter the electrical box and
do not interfere with the fully opened roof.
A
B
The home generator is supplied with a base that, unless
mandated by local code, does not require a concrete slab.
NOT
for
REPRODUCTION